DHC Smoke Detector

DATASHEET

DHC Smoke Detector

Product Name : Wired Smoke Detector
Model : SD-604 2 wired
Voltage DC : 9V~35V( Support: DC40~60V)
Current : Standby current: ≤50uA
Alarm Current : 20~25 mA @12V ; 40~50 mA @24V
Sensitivity : 0.08~0.16 dB/m
Material : EN54-7:2008
Color : White
Standard : EN54-7:2008
Certificate : CE
Dimension : Ø99 * H43.5mm

 Product Parameter】



•   Operating voltage :                               9V~35V( Support: DC40~60V)                                                         •   Standby current :                                                             ≤ 50 uA


•   Sensitivity :                                                               0.08~0.16 dB/m                                                             •   Alarm current :                   20~25 mA @12V ;   40~50 mA @24V


•   Standard:                                                                      EN54-7:2008                                                              •   Indicator LED of alarm :                                    red LED Light on


•   Certificate:                                                                               CE                                                          •   Material :                                                                                ABS


•   Operation temperature :                                                  0℃~50℃                                                             •   Operation humidity :                      ≤ 95%RH(no condensation)


•   Dimension :                                                              Ø99 * H43.5mm                                                                   


                 


【 Product Introduction 】


This product named Photoelectric smoke detector (hereinafter called detector) detects the smoke by a couple of infrared diodes.

The principle of detecting is granule in the smoke can reflect infrared light. Infrared diodes are placed in the special chamber.

The chamber can shield external light, but doesn’t affect the smoke into it. While there is no smoke, the diode can receive very weak infrared light. When the smoke entering the chamber, diode can receive more and more light, and the detector can give out alarm signal when the smoke attains the certain density.

In order to reduce the interference and lower power consumption, the emitting circuit adopts the pulse signal. The product in accordance with the networking approach is divided into 2-wire and 4-wire detectors.