DATASHEET
INSTRUCTION MANUAL

ORION MINI-REP V2

The ORION MINI-REP V2 provides remote control and system display status from multiple locations to an ORION based fire alarm system. All Fire, Fault, Test and Disabled conditions are displayed. The user is able to control all functions at Access Levels 1 and 2. Access to Level 2 is via the same four-digit code used on the ORION V2.

Its reduced dimensions make it ideal for installation in reception areas or security booths where it would be impractical and unattractive to install a full-size control panel. The repeater panel can be connected to the main panel using four different communication technologies: RS232, RS485, fibre optics and TCP/IP.

TECHNICAL SPECIFICATIONS

SUPPLY VOLTAGE(21-29V DC) 24V DC nominal
SUPPLY CURRENT40 mA
CONNECTIONSSupply: +/- ; Communication: Tx/Rx & GND
REPEATER NETWORKRS-232, RS-485, FO or TCP/IP * – 1 Display & Control + 3 Display Only
PANEL COMPATIBILITYORION
MAX. HUMIDITY95% RH Non-Condensing
OPERATING TEMPERATURE-10ºC to 50ºC
COLOUR / CASE MATERIALWhite or Red / ABS
WEIGHT1.4 Kg
DIMENSIONS256 (L) x 194 (W) x 75 (H) mm