Data sheet
INSTRUCTION MANUAL

Flame Detectors

GFE has added flame detectors to our range, providing an additional high-quality and competitive solution to our customers.

This new range has three models covering UV and IR wavelengths, namely UV, triple IR and combined UV/IR detection.

With CPR and ATEX certification, these products it will be a good option for the majority of scenarios where flame detection technology is required.

TECHNICAL SPECIFICATIONS

POWER12-24 Vdc (10-28 Vdc)
CURRENT NORMAL25 mA at 24 Vdc
STARTUP TIME<10 sec
RELAY OUTPUTS / ALARM RELAYDe-energized during normal operation, no alarm, SPDT, 30 Vdc – 2 A, 60 W max.
RELAY OUTPUTS / FAULT RELAYEnergized during normal operation, no fault, SPDT, 30 Vdc – 2 A, 60 W max.
HOUSINGGlass Reinforced Polyester (GRP), Lid screw tightening torque 2 nm minimum
INGRESS PROTECTIONIP65
OPERATING TEMPERATURE-40ºC to 70ºC
DIMENSIONS125 x 80 x 57 mm
WEIGHT280 g
COLORRed & Whit